“Combi” Gas-Fired
Boiler/Water Heater
Model 35 BF
Installation and
Operating Instructions
CLIOM-2
315 Oser Avenue • Hauppauge, NY 11788
Tel: (631) 694-1800 • Fax: (631) 694-1832
www.embassyind.com
Page view 0
1 2 3 4 5 6 ... 35 36

Summary of Contents

Page 1 - Operating Instructions

“Combi” Gas-Fired Boiler/Water HeaterModel 35 BFInstallation and Operating InstructionsCLIOM-2315 Oser Avenue • Hauppauge, NY 11788Tel: (631) 694-1800

Page 2

10ENG4. The distance between the intake air and the smoke pipe must be within 300 mm (12 in) - (see fig. below).5. The head loss of the smoke pipe c

Page 3 - User and Care Guide

11ENG2.7.1 Separate flue kit (fig. 8)The separate flue kit code 8089909 is sup-plied with an intake diaphragm which must be used as shown in fig. 8/

Page 4 - 1 DESCRIPTION OF THE BOILER

12ENGmax 0,5 mmax 0,5 mC12B52149C52B52C32C42321110C82B2265612311103718313233 213236318 3Figure 9/aIMPORTANT: In type C52 the outlet and inlet flues mu

Page 5

13ENGOutlet terminals for forced draft systems may be located on the outer walls of the buildings. Table 2 shows approximate, non-binding minimum dist

Page 6 - Figure 2

14ENG2.8.2 Instructions special stainless steel venting system for use with Category III appliancesZ-FLEX recommends that an experienced pr

Page 7 - 2 INSTALLATION

15ENGintegrity has remained during shipping. Gaskets must be in the proper position or flue gases could leak resulting in carbon monoxide poisoning.1.

Page 8

16ENG(see figure 6/a below) 1. Penetrating a combustible wall requires the use of a wall thimble. The pipe may be mortared in directly without using

Page 9

17ENG(see figure 6/b - 6/d)NOTE: The vent termination must be at least 3 ft. (1 m) to a maximum of 6ft. above the roof line and 2 ft. (.61 m) higher t

Page 10 - Frontal view

18ENGNOTE: When Z-Vent must be extended above the roof line more than six (6) feet the Guy Band must be used to support the system.1. Install the Gu

Page 11

19ENGNOTE: A masonry chimney flue may be used to route Z-VENT if no other appliance vents directly into the same flue without a liner. Prior to beginn

Page 12 - (12inches)

Fonderie Sime S.p.A. Via Garbo, 27 – 37045 LEGNAGO (VR)declares that:a) The materials used in the interior of the boiler are suitable for the use of

Page 13 - MINIMUM DISTANCE mm feet

20ENGCode Part I, CSA C22.1, Electrical Code. If you must replace the electric power cable supplied with the boiler, order it exclusively from Sime. T

Page 14 - SVSHTX03

21ENGCN6CN2CN7KEYF Fuse (1.6 AT)PI C.H. pumpEV1-2 Gas valve coilV FanPF Smoke pressure switchVP Divertor valveM ModulatorSM C.H. sensorSS D.H.W. pr

Page 15

22ENG3.1 ELECTRONIC BOARDThe electronic boards are manufactured in compliance with the ANSI and Canadian direc-tives. They are supplied with 120V and

Page 16

23ENG3.3 ELECTRONIC IGNITIONIgnition and flame detection is controlled by an electrode located on the burner. These guarantee maximum safety with inte

Page 17

24ENGTo obtain the maximum head available to the system, turn off the by-pass by turning the union to the vertical position (fig. 17/a).3.7 ELECTRICAL

Page 18

25ENG4.2 ADJUSTMENT OF D.H.W. FLOW RATETo adjust the D.H.W. flow rate, use the flow rate adjuster (5 fig. 5). Remember that the flow rates and corre

Page 19

26ENG1. Close the gas cock.2. Disassemble the burner manifold (3).3. Replace the main nozzles (6) supplied in a kit, inserting the copper washer (4).

Page 20

27ENGcleaning the heat exchanger or the bur-ners, chemical products or steel brushes MUST NOT BE USED. Make sure that the tops of the burners with th

Page 21 - 2.9.3 Wiring diagram

28ENGRadiators fail to heat up in winter.1. The rotary switch is on “Summer”; switch to “Winter”.2. The room stat is set too low or needs repla-cing b

Page 22 - 3 CHARACTERISTICS

29ENG5 EXPLODED VIEWS / VUES ÉCLATÉES

Page 23 - Figure 17

3ENGInstallation Instruction and User and Care GuideTABLE OF CONTENTS1 DESCRIPTION OF THE BOILER 41.1 INTRODUCTION 41.2 DIMENSIONS 42 INSTALLATION

Page 24 - 4 USE AND MAINTENANCE

30ENGFonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.itETONLEDOMNOITPIRCSEDEDOCN

Page 25

31ENGFonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.itETONLEDOMNOITPIRCSEDEDOCN

Page 26 - ...at last to pull

32ENGFonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.itETONLEDOMNOITPIRCSEDEDOCN

Page 27 - Spia lampeggiante

33ENGFonderie Sime S.p.A. - Via Garbo, 27 - 37045 Legnago (Verona) - Tel. +39-0442-631111 - Fax +39-0442-631292 - www.sime.itETONLEDOMNOITPIRCSEDEDOCN

Page 28

34ENG

Page 29

35ENG

Page 30

315 Oser Avenue • Hauppauge, NY 11788Tel: (631) 694-1800 • Fax: (631) 694-1832www.embassyind.com

Page 31

4ENG1.1 INTRODUCTIONCelsior boilers are gas-fired thermal applian-ces for central heating and domestic hot water production, designed and manufactu-

Page 32

5ENGCLEARANCES FROM COMBUSTIBLE MATERIALS:Bottom: 0 mm (0 in.)Sides: 0 mm (0 in.)Rear: 0 mm (0 in.)Front: 0 mm (0 in.)Top: 0 mm (0 in.)Flue (superate

Page 33

6ENG61211109875431131419KEY1 Fan2 Main exchanger3 Combustion chamber4 Gas valve5 D.H.W. plate exchanger6 Divertor valve7 C.H. sensor (SM)8 100°C sa

Page 34

7ENGThe installation must conform to the require-ments of the Authority having jurisdiction or, in the absence of such requirement, to the National Fu

Page 35

8ENGpipe size of other materials. The sections of the piping making up the system must be such as to guarantee a supply of gas sufficient to cover the

Page 36

9ENGpressure, with the system cold, must be betwe-en 1 and 1.2 bar (14.5 and 17.4 psi). During system filling you are recommended to keep the main sw